Amps to kW Calculator

For single-phase or DC power, kW = amps × volts × power factor ÷ 1,000. For three-phase, multiply by √3 (1.732) as well. The default 30 A at 240 V single-phase with a power factor of 1 is 7.2 kW, and 80% of that, 5.76 kW, is the maximum continuous load on a 30 A breaker.

By Izhar Ahmad DanishUpdated Sources cited

A
V

Single phase: kW = A × V × PF ÷ 1,000. Three phase: kW = √3 × A × V × PF ÷ 1,000. Resistive loads (heaters) have PF 1; motors are often 0.8–0.9.

Real power

7.2 kW

Watts7,200 W
Apparent power7.2 kVA
Max continuous load on this breaker (80%)5.76 kW

Key numbers

  • Single phase: kW = A × V × PF ÷ 1,000
  • Three phase: kW = √3 × A × V(line-to-line) × PF ÷ 1,000
  • 30 A at 240 V = 7.2 kW; continuous limit 5.76 kW (80%)
  • 30 A at 480 V three-phase = 24.9 kW at PF 1
On this page
  1. How to use the Amps to kW
  2. How to convert amps to kilowatts
  3. Amps to kW conversion table (PF = 1)
  4. Amps vs kW: what’s the difference?
  5. Converting kW back to amps
  6. What affects the result
  7. History of the ampere and three-phase power
  8. References
  9. Single-phase vs three-phase in plain terms
  10. Frequently asked questions

How to use the Amps to kW

  1. 1Enter your numbersFill in current (A), voltage (V), circuit and power factor. Every field starts with a typical value you can overwrite.
  2. 2Check the assumptionsSingle phase: kW = A × V × PF ÷ 1,000. Three phase: kW = √3 × A × V × PF ÷ 1,000. Resistive loads (heaters) have PF 1; motors are often 0.8–0.9.
  3. 3Read the resultsThe calculator shows real power, watts, apparent power and max continuous load on this breaker (80%), and updates as you type.
  4. 4Use the resultCompare it with your bill, a quote or a product spec sheet before you buy or install anything.

Results update as you type. Back to the calculator ↑

This amps to kW calculator converts electric current into real power for single-phase, three-phase and DC circuits. Enter the current in amps, the voltage, the circuit type and the power factor. You get kilowatts, watts, apparent power in kVA, and the continuous load the breaker can carry.

How to convert amps to kilowatts

Current alone does not tell you power. You also need the voltage, and for AC loads, the power factor (PF), the ratio of real power to apparent power as defined in IEEE Std 1459-2010:

  • Single-phase AC or DC: kW = A × V × PF ÷ 1,000
  • Three-phase AC: kW = √3 × A × V × PF ÷ 1,000, where V is line-to-line voltage and √3 ≈ 1.732
  • Apparent power: kVA = kW ÷ PF
  • Continuous breaker load: 80% of the circuit’s kW capacity

For DC circuits there is no power factor, so leave it at 1.

Worked example with the default values

  1. Current 30 A, voltage 240 V, single phase, PF 1
  2. Real power: 30 × 240 × 1 ÷ 1,000 = 7.2 kW (7,200 W)
  3. Apparent power: 7.2 ÷ 1 = 7.2 kVA
  4. Continuous load limit at 80%: 7.2 × 0.8 = 5.76 kW

Switch to three-phase at 480 V and the same 30 A gives 1.732 × 30 × 480 ÷ 1,000 = 24.9 kW.

Amps to kW conversion table (PF = 1)

Amps 120 V single 240 V single 208 V three-phase 480 V three-phase
10 A 1.2 kW 2.4 kW 3.6 kW 8.3 kW
15 A 1.8 kW 3.6 kW 5.4 kW 12.5 kW
20 A 2.4 kW 4.8 kW 7.2 kW 16.6 kW
30 A 3.6 kW 7.2 kW 10.8 kW 24.9 kW
40 A 4.8 kW 9.6 kW 14.4 kW 33.3 kW
50 A 6.0 kW 12.0 kW 18.0 kW 41.6 kW
100 A 12.0 kW 24.0 kW 36.0 kW 83.1 kW

For a power factor below 1, multiply the table value by the PF. A 30 A, 240 V motor at PF 0.85 delivers 7.2 × 0.85 = 6.12 kW.

Amps vs kW: what’s the difference?

Amps measure current, the rate at which electric charge flows; kilowatts measure power, the rate at which energy is used. Voltage links them: the same 30 A is 3.6 kW at 120 V but 7.2 kW at 240 V. Breakers and wires are rated in amps because conductor heating depends on current, while appliances and bills use kW and kWh. To turn kW into energy over time, multiply by hours to get kWh.

Converting kW back to amps

Rearrange the formula: amps = kW × 1,000 ÷ (V × PF) for single-phase, and divide again by 1.732 for three-phase. A 7.2 kW Level 2 EV charger on 240 V draws 30 A. Use the kW to amps calculator to go the other way, with a conversion table and the next standard breaker size for continuous loads under the National Electrical Code.

What affects the result

  • Voltage. US homes have 120 V and 240 V circuits; commercial buildings often use 208 V or 480 V three-phase. Measured voltage can sit a few percent above or below nominal.
  • Power factor. Heaters, ovens and incandescent lamps are near 1. Motors, compressors and some LED drivers are lower; the DOE notes motor power factor falls at light load.
  • Line vs phase voltage. The three-phase formula above uses line-to-line voltage. If you only know phase-to-neutral voltage, multiply amps × volts × PF × 3 instead.
  • Starting current. Motors draw several times their running current for a moment at startup; size breakers for that, not just running kW.

Watch out

This calculator is for estimates. Have a licensed electrician size breakers and wiring, especially for EV chargers, heat pumps, solar inverters and other renewable energy equipment.

Once you know the kW, use the kW to watts converter for other units, or the electricity cost calculator to see what running the load costs. To size backup power for a load, try the UPS calculator. The guide what is a kilowatt-hour explains how kW of power become kWh on your bill.

History of the ampere and three-phase power

The ampere honours André-Marie Ampère, whose work on electrodynamics in the 1820s founded the science of electric current. An international convention at the 1881 International Exposition of Electricity in Paris established the ampere as a standard unit, and since the 2019 SI revision it is defined by fixing the elementary charge (Ampere; NIST SP 330). The three-phase formula in this calculator comes from the polyphase systems of the late 1880s. Nikola Tesla’s US Patent 381,968 for an electro-magnetic motor was granted on 1 May 1888, and Mikhail Dolivo-Dobrovolsky at AEG developed a three-phase generator and motor in 1888. In 1891 he transmitted three-phase power about 176 km from Lauffen to the International Electro-Technical Exhibition in Frankfurt (Dolivo-Dobrovolsky), the demonstration that set three-phase on the way to becoming the standard for grids and industry.

Portrait of Nikola Tesla
Nikola Tesla (1856–1943)Patented polyphase AC induction motors (1888).Photo: Napoleon Sarony. Public domain, via Wikimedia Commons.
Year Milestone
1881 Ampere established as a unit of current (Paris)
1888 Tesla polyphase motor patent; Dolivo-Dobrovolsky three-phase motor
1891 Lauffen–Frankfurt three-phase transmission, about 176 km
2019 Ampere redefined via the elementary charge

References

  • IEEE Std 1459-2010. “IEEE Standard Definitions for the Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced Conditions.” doi:10.1109/IEEESTD.2010.5439063
  • U.S. Department of Energy. Determining Electric Motor Load and Efficiency (fact sheet). energy.gov
  • Newell, D. B. & Tiesinga, E. (eds.) (2019). The International System of Units (SI). NIST Special Publication 330. doi:10.6028/NIST.SP.330-2019

Single-phase vs three-phase in plain terms

Single-phase power uses one alternating voltage and is what almost all US homes receive, split into 120 V and 240 V circuits. Three-phase power uses three voltages offset in time, which delivers more power through the same size of wire. That is why factories, large commercial buildings, big heat pumps and many solar inverters above residential size use it. If your panel has three hot bus bars, you have three-phase service.

FAQ

Frequently asked questions

How do I convert amps to kW?

Multiply amps by volts and by the power factor, then divide by 1,000. A 20 amp, 120 volt circuit with a resistive load is 20 × 120 × 1 ÷ 1,000 = 2.4 kW. For three-phase power, multiply the result by 1.732 and use line-to-line voltage.

How many kW is 30 amps?

At 240 volts single-phase and a power factor of 1, 30 amps is 7.2 kW. At 120 volts it is 3.6 kW. At 480 volts three-phase it is about 24.9 kW. You always need the voltage to convert amps to kilowatts.

What is power factor?

Power factor is the ratio of real power (kW) to apparent power (kVA). Resistive loads such as heaters and incandescent lamps have a power factor of 1. Motors and some electronics are lower, often 0.8 to 0.9, so they draw more amps for the same real power.

Why is the maximum continuous load 80% of the breaker?

In the US, the National Electrical Code generally sizes circuits so that continuous loads, those running three hours or more, use no more than 80 percent of the breaker rating. That is why a 40 amp circuit is used for a 32 amp EV charger.

How many amps is 1 kW?

At 120 volts single-phase, 1 kW draws about 8.3 amps; at 240 volts, about 4.2 amps; at 480 volts three-phase with PF 1, about 1.2 amps. Divide 1,000 by the volts (and by 1.732 for three-phase) to get amps.

How do I convert amps to kWh?

Convert amps to kW first, then multiply by the hours the load runs. A 15 amp, 120 volt resistive load is 1.8 kW; running for 3 hours it uses 1.8 × 3 = 5.4 kWh. For a battery rated in amp-hours, use kWh = Ah × volts ÷ 1,000 instead.

7 Sources

  1. NFPA 70, National Electrical Code (continuous load provisions)
  2. U.S. DOE, Determining electric motor load and efficiency
  3. IEEE Std 1459-2010, Definitions for the measurement of electric power quantities
  4. Wikipedia, Ampere (history of the unit)
  5. Wikipedia, Mikhail Dolivo-Dobrovolsky
  6. Tesla, N., US Patent 381,968: Electro-magnetic motor (1888)
  7. NIST, SP 330: The International System of Units (2019)

Last updated October 25, 2026. Part of our renewable energy toolkit. Found an error? Tell us.